Model ESB001.LED.230Vac
Limiting Peak current 43A for Ton=250ms
Limiting RMS-value 30,1A for Ton=250ms
Limiting Cycle Interval 1000ms (3x/minute)
Low Voltage Detection Toff=500ms
Input Voltage 184 – 264Vac, 16 1/3 – 440Hz
Nominal voltage 220 – 240Vac
AC Continuous Current 16A
Power Consumption 1,1W
Load capacity 5000uF
Connectors Spring-type-terminal 0,13 – 4mm² / 26 – 12 AWG
Ambient Opearting Temperature -40°C – +55°C no derating
Cooling Natural convection
Dimensions (WxHxD) 17,9 x 89,5 x 62,8 mm (1TE)
Safety Standards EN61010-1, EN61010-2-201, EN62368-1, EN60204-1, EN60950-1
Special Features Temperature protected (fuse)
Fire protected
Accuracy ±5%, independent from ambient temperature
Capacitive loads
Bypass circuit
4000m / 13123 ft. above sea level